Brand: Phoenix Contact
Category: Surge Protection Devices
- Model: 2905333
- Plug-in surge arrester, in accordance with Type 2/Class II, for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact.
- Spark-gap Technology
- Plug-in surge arrester, in accordance with Type 2/Class II, for 1-phase power supply networks
- With separate N and PE (3-conductor system: L1, N, PE), with remote indication contact

|
Nominal Voltage UN |
240 V AC (TN-S) |
|
240 V AC (TT) |
|
|
Nominal Frequency fN |
50 Hz (60 Hz) |
|
Maximum continious operating voltage Uc (L-N) |
350 V AC |
|
Maximum continious operating voltage Uc (L-PE) |
350 V AC |
|
Maximun continious operating voltage Uc (N-PE) |
264 V AC |
|
Rated load current lL |
40 A (Biconnect M4 fork-type cable lug 6 mm²) |
|
63 A (TWIN ferrule 2 x 10 mm²) |
|
|
Residual current lPE |
≤ 1 µA |
|
Nominal discharge current In (8/20) µs |
20 kA |
|
Maximum discharge current Imax (8/20) µs |
40 kA |
|
Follow current interrupt rating Ifi (N-PE) |
100 A (264 V AC) |
|
Short-circuit current rating ISCCR |
25 kA (for a backup fuse of up to 315 A gG) |
|
50 kA (for a backup fuse of up to 200 A gG) |
|
|
Voltage protection level Up (L-N) |
≤ 1.5 kV |
|
Voltage protection level Up (L-PE) |
≤ 1.9 kV |
|
Voltage protection level Up (N-PE) |
≤ 1.5 kV |
|
Residual voltage Ures (L-N) |
≤ 1.5 kV (at In) |
|
≤ 1.3 kV (at 10 kA) |
|
|
≤ 1.2 kV (at 5 kA) |
|
|
≤ 1.1 kV (at 4 kA) |
|
|
≤ 1 kV (at 2 kA) |
|
|
Residual voltage Ures (L-PE) |
≤ 1.9 kV (at In) |
|
≤ 1.5 kV (at 10 kA) |
|
|
≤ 1.4 kV (at 5 kA) |
|
|
≤ 1.3 kV (at 4 kA) |
|
|
≤ 1.2 kV (at 2 kA) |
|
|
Residual voltage Ures (N-PE) |
≤ 0.5 kV (at In) |
|
≤ 0.5 kV (at 10 kA) |
|
|
≤ 0.5 kV (at 5 kA) |
|
|
≤ 0.5 kV (at 4 kA) |
|
|
≤ 0.5 kV (at 2 kA) |
|
|
TOV behavior at UT (L-N) |
415 V AC (5 s / withstand mode) |
|
457 V AC (120 min / safe failure mode) |
|
|
TOV behavior at UT (N-PE) |
1200 V AC (200 ms / withstand mode) |
|
Response time tA (L-N) |
≤ 25 ns |
|
Response time tA (L-PE) |
≤ 100 ns |
|
Response time tA (N-PE) |
≤ 100 ns |
|
Max. backup fuse with V-type through wiring |
40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
|
63 A (gG / TWIN ferrule 2x 10mm²) |
|
|
Max. backup fuse with branch wiring |
315 A (gG) |