- Tesys Deca thermal overload relays are designed to protect a.c. circuits and motors against overloads.
- New modern look & feel of all machines
- Easier to install and operate with multi-standard screws
- Digital customer experience for technical documents
- Maintenance guide via EcoStruxureTM Facility Expect
- TeSys LRD thermal overload relay, 13A/690V, thermal setting range 9-13A, tripping class 10A, for protection of 3-phase motors 5.5kW@400V.
- Differential device with phase failure and load unbalance detection.
- It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling.
- Settings are protected by a transparent cover lockable by sealing.
- Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D12-D38.
- Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately).
- Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
| Range | TeSys |
| TeSys Deca | |
| product name | TeSys LRD |
| TeSys Deca | |
| Product or component type | Differential thermal overload relay |
| Device short name | LRD |
| Relay application | Motor protection |
| Product compatibility | LC1D18 |
| LC1D38 | |
| LC1D32 | |
| LC1D12 | |
| LC1D25 | |
| network type | DC |
| AC | |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 9…13 A |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA |
| Power circuit: 600 V conforming to UL | |
| Power circuit: 690 V conforming to IEC 60947-4-1 |