Brand: Phoenix Contact
Category: UPS, Batteries & Power Supply
- Model : 2902999
- Primary-switched UNO POWER power supply for DIN rail mounting,
- Input: 1-phase, Input voltage range 85 V AC ... 264 V AC
- Output: 12 V DC/55 W.
- With high power density, compact UNO POWER power supplies are the ideal solution for loads up to 240 W, particularly in compact control boxes

|
Nominal input voltage range |
100 V AC ... 240 V AC |
|
Input voltage range |
85 V AC ... 264 V AC |
|
Input voltage range AC |
85 V AC ... 264 V AC |
|
Voltage type of supply voltage |
AC |
|
Inrush current |
< 30 A (typ.) |
|
Inrush current integral (I2t) |
< 0.5 A2s (typ.) |
|
AC frequency range |
50 Hz ... 60 Hz -10 % ... +10 % |
|
Frequency range (fN) |
50 Hz ... 60 Hz ±10 % |
|
Mains buffering time |
> 20 ms (120 V AC) |
|
> 90 ms (230 V AC) |
|
|
Current consumption |
typ. 1.3 A (100 V AC) |
|
typ. 0.6 A (240 V AC) |
|
|
Nominal power consumption |
127 VA |
|
Protective circuit |
Transient surge protection; Varistor |
|
Power factor (cos phi) |
0.49 |
|
Typical response time |
< 1 s |
|
Input fuse |
2 A (slow-blow, internal) |
|
Permissible backup fuse |
B6 B10 B16 |
|
Recommended breaker for input protection |
6 A ... 16 A (Characteristics B, C, D, K) |
|
Efficiency |
typ. 87 % (120 V AC) |
|
typ. 88 % (230 V AC) |
|
|
Output characteristic |
HICCUP |
|
Nominal output voltage |
12 V DC ±1 % |
|
Nominal output current (IN) |
4.6 A (-25 °C ... 55 °C) |
|
Derating |
55 °C ... 70 °C (2.5%/K) |
|
Feedback voltage resistance |
< 25 V DC |
|
Protection against overvoltage at the output (OVP) |
≤ 25 V DC |
|
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
|
|
< 0.1 % (change in input voltage ±10 %) |
|
|
Residual ripple |
< 30 mVPP (with nominal values) |
|
Output power |
55 W |
|
Maximum no-load power dissipation |
< 0.3 W |
|
Power loss nominal load max. |
< 8 W |
|
Rise time |
< 0.5 s (UOUT (10 % ... 90 %)) |
|
Response time |
< 2 ms |
|
Connection in parallel |
yes, for redundancy and increased capacity |
|
Connection in series |